Model NO. YCQ9M
Max. Voltage AC 400V
Electrical Life 1000
Rated Inpulse Withstand Voltage(Kv) 8
Original Ycb9m
Whether The Smart Yes
Transport Package CNC Packingstandard Packaging
Trademark CNC
Origin Zhejiang, China
Production Capacity 80000 Unit/Units Per Week
Product Description

CNC Intelligent ATS Generator Automatic Transfer Switch Electric Manual

Product Description


1.Ensure un-interruptible service of critical electric powerWhen overvoltage, under-voltage or phase failure occur to a power supply, it will automatically switch over to another power supply or start the electric generator. It is mainly used in hospital, shopping mall, bank, hotel, high buildings and fire control where long time power disconnection is not allowed and ceaseless power supply is needed.2,.Full automatic power supply changeover systemIt is equipped with three changeover methods including self-throwing and self- reset (power network to power network), self-throwing and not self-reset (power network to power network), self-throwing and self-reset (power network to power generation), in order to satisfy different power changeover requirement.3.IntelligentIt has communication interface with built-in RS485, and has two kinds of communication agreement including MODBUS-RUS and electric meter 1997, which can realize real time data upload, distance data configuration and condition monitor, and can achieve the function of telecommand, telemetering, remote control, and remote regulating. Remote vision can be achieved through matching intelligent power distribution system.4.Safe and reliable, and have fire control linkage functionWhen fire disaster occurs to no fire control load, fire protection control center can send signal to intelligent controller, cut off double power supply, ensure fire disaster load to break.

CNC Intelligent ATS Generator Automatic Transfer Switch Electric Manual

CNC Intelligent ATS Generator Automatic Transfer Switch Electric Manual


CNC Intelligent ATS Generator Automatic Transfer Switch Electric Manual

CNC Intelligent ATS Generator Automatic Transfer Switch Electric Manual

CNC Intelligent ATS Generator Automatic Transfer Switch Electric Manual

Life(N-R-N circle) and Specifications of Automatic Transfer Switch

Model numberYCQ9M-63~250YCQ9M-400YCQ9M-630
Electrical life (t)100010001000
Mechanical life (t)500030002000
Total life (t)600040003000
Rated dutyuninterrupted duty
Under-voltage switching setpoint180~210V
Over-voltage switching setpoint230~280V
Contacts switching time≤3s
Switching return delay time0.1~99.9s(Adjustable)


Main Technical Parameter of Automatic Transfer Switch

SpecificationsExecution breakerRated current (A)Rated voltage (V)Rated impulse withstand voltage (kV)Rated short-circuit making capacity (kA)Rated short-circuit breaking capacity (kA)
63M/3PYCM1-63M/3P16/25/32/40/50/63
400

8
52.525
63M/4PYCM1-63M/4P
125M/3PYCM1-100M/3P16/25/32/40/506330
63/80/100/125
125M/4PYCM1-100M/4P
250M/3PYCM1-225M/3P100/125/140/16073.535
180/200/225/250
250M/4PYCM1-225M/4P
400M/3PYCM1-400M/3P225/250/31510550
350/400
400M/4PYCM1-400M/4P
630M/3PYCM1-630M/3P400/500/63010550
630M/4PYCM1-630M/4P